The boilers from the KP series are intended for generation of saturated steam with working pressure up to 0,05 МРа and temperature up to 110°С.
By customer request, different additional equipment items can be offerred, such as containers, water softener installations, fuel oil pump and heating unit when heavy oil is used, as well as gas train (line) for boilers working with nature gas, and others.
See pictures ► Gallery
Technical charactersitics
| No | Boiler type | Rated steam output | Rated heat output | Working pressure | Saturated steam temperature | Feed water temperature | Efficiency | Weight, without auxilliary equipment |
| kg/h |
Gcal/h kW |
MPa | °C | °C | % | kg | ||
| 1. | KP 0,1 | 171 |
0,1 116,3 |
0,05 | 110 | 60 | 92 | 1144 |
| 2. | KP 0,15 | 257 |
0,15 174,4 |
0,05 | 110 | 60 | 92 | 1534 |
| 3. | KP 0,25 | 428 |
0,25 290 |
0,05 | 110 | 60 | 92 | 1724 |
| 4. | KP 0,35 | 599 |
0,35 407 |
0,05 | 110 | 60 | 92 | 2480 |
| 5. | KP 0,55 | 942 |
0,55 639,6 |
0,05 | 110 | 60 | 92 | 2890 |
| 6. | KP 0,65 | 1113 |
0,65 755,9 |
0,05 | 110 | 60 | 92 | 3200 |
| 7. | KP 1,0 | 1712 |
1,0 1163 |